MR20-EI-1612R
16 channel digital input, NPN/PNP type; 12 channel relay output
Supports rich protocols, all-round isolation, grounding protection design, high signal density, up to 64 points, plug-in terminals, easy maintenance
Technical parameter
| product description | 16 channel digital input, NPN/PNP type; 12 channel relay output |
| bus protocol | EtherNET/IP |
| Distance | ≤100 m(Station distance) |
| transfer rate | 100/10Mbps,Adaptive, full duplex |
| network interface | 2×RJ45,Switching function |
| Output points | 12 |
| type | Relay, dry contact |
| Maximum switching voltage | 30VDC/277VAC |
| Rated current at each point (maximum) | 2A 250VAC/30VDC |
| Surge voltage (between coil and contact)间) | 10KV(1.2/50μs) |
| Isolation (on-site and logical side) | 1500V AC Continuous for 1 minute (coil and contact) No (coil and logic side) |
| Current at each common terminal (maximum) | 4A |
| Mechanical Endurance | 2×10^7次 |
| Contact life under rated load | 1 × 105 times (resistive load, room temperature, 1.5 seconds on and 1.5 seconds off) |
| Contact life under rated load | 1 × 105 times (resistive load, room temperature, 1.5 seconds on and 1.5 seconds off) |
| rated voltage | 24 VDC(18V~30V) |
| Number of signal points | 16 |
| signal type | Source type/leakage type |
| Input Current | 2.3 mA |
| isolation method | Optocoupler isolation |
| Isolation and voltage resistance | 500 VAC |
| Anti reverse connection protection | support |
| Electrical isolation | 500 VAC |
| size | 105×77×25 mm |
| operation temperature | -25 ~ +60℃ |
| storage temperature | -40 ~ 85℃ |
| relative humidity | 95%,No condensation |
| protection grade | IP20 |
Pertinent Literature
Operation guidance
Related cases